Hioki PW3360-21 Clamp-On Power Logger, 90 to 780V, Harmonic Analysis

Hioki PW3360-21 Clamp-On Power Logger, 90 to 780V, Harmonic Analysis

SKU: PW3360-21

$1,874.77

Availability: Regular Price Hioki PW3360-21 Offers With this Hioki PW3360-21 Clamp-On Power Logger, you can safely and accurately measure single- to 3-phase lines. The logger is capable of measuring 90 to 780 V, and you can store the data on SD or SDHC cards. The Quick Set function provides an on-screen guide to ensure you make the correct connection. Features Accurately and safely measures power on single- to 3-phase 4-wire circuits Capable of

1
Request a Quote
Secure Checkout
Fast Shipping
Authorized Dealer

Availability: Regular Price

Hioki PW3360-21 Offers

With this Hioki PW3360-21 Clamp-On Power Logger, you can safely and accurately measure single- to 3-phase lines. The logger is capable of measuring 90 to 780 V, and you can store the data on SD or SDHC cards. The Quick Set function provides an on-screen guide to ensure you make the correct connection.

Features

  • Accurately and safely measures power on single- to 3-phase 4-wire circuits
  • Capable of measuring 90 to 780 V signals
  • Use SD or SDHC memory card to store months of data
  • Ensure you're making the correct connection with the Quick Set function that uses an on-screen guide
  • Compact design is slim for simple portability
  • Displays values as a graph
  • Move the cursor on the demand and trend graph displays to review maximum, minimum and average values
  • Capable of measuring harmonic voltage level, harmonic current level, harmonic power level, content percentage, phase angle and total harmonic distortion (THD-F or THD-R) up to the 40th order
  • LAN and USB 2.0 interfaces
  • CE-compliant design

Note: At least one optional current sensor is necessary to measure current or power parameters. To store measurement data, use only the guaranteed SD card sold by Hioki.

Hioki PW3360-21 Specifications

Specifications

Measurement Line 50/60 Hz
Measurement Circuits Single-phase 2-wire (1/2/3 circuits), single-phase 3-wire (1 circuit), 3-phase 3-wire (1 circuit), 3-phase 4 wires (1 circuit)
Number of Channels 1 to 3 (current only)
Measurement Items Voltage RMS, current RMS, voltage fundamental wave value, current fundamental wave value, voltage fundamental wave phase angle, current fundamental wave phase angle, frequency (U1), voltage waveform peak (absolute value), current waveform peak (absolute value), active power, reactive power (with lag/lead display), apparent power, power factor (with lag/lead display) or displacement power factor (with lag/lead display), active energy (consumption, regeneration), reactive energy (lag, lead), energy cost display, active power demand quantity (consumption, regeneration), reactive power demand quantity (lag, lead), active power demand value (consumption, regeneration), reactive power demand value (lag, lead), power factor demand, pulse input, harmonic voltage level, harmonic current level, harmonic power level, content percentage, phase angle and total harmonic distortion (THD-F or THD-R) up to the 40th order
Voltage Range 600 VAC (effective measurement range: 90 to 780 V)
Current Range 500 mA to 5 kA AC (depends on current sensor in use), 50 mA to 5 A AC (leak clamp on sensor only)
Power Ranges 300 W to 9 MW
Accuracy Voltage: ±0.3% of reading ±0.1% full scale, Current: ±0.3% of reading ±0.1% full scale + clamp sensor, Active Power: ±0.3% of reading ±0.1% full scale + clamp sensor (at power factor = 1)
Display Refresh Rate 0.5 seconds
Data Save Destination SD card, internal memory (at real time)
Data Save Intervals 1 to 30 seconds, 1 to 60 minutes, 14 selections
Save Items Measurement Value Save: Average only/average, max/min value, Screen Copy: BMP form (saved every 5 minutes at minimum interval time), Waveform Save: binary waveform data, Harmonic Data Save: average only/average, maximum, minimum value in binary format
Interface SD/SDHC memory card, 100Base-TX LAN, USB 2.0, Pulse output: proportional to active power consumption when measuring integral power consumption, isolated open-collector signal
Functions Connection check, quick set navigation guide, clock, pulse input
Power Supply 100 to 240 VAC 50/60 Hz 40 VA Z1006 AC adapter, 7.2 VDC 3 VA 9459 battery pack
Product Length 1.89" (48 mm) without PW9002, 2.65" (67.2 mm) with PW9002
Product Width 7.09" (180 mm)
Product Height 3.94" (100 mm)
Product Weight 19.4 oz (550 g) without PW9002, 29.3 oz (830 g) with PW9002
Manufacturer Warranty 3-year limited

What's included with the Hioki PW3360-21

  • Clamp-On Power Logger
  • L9438-53 Voltage Cord Set
  • Z1006 AC Adapter
  • USB Cable
  • Color Clip Set
  • 5 x Spiral Tubes for Grouping Clamp Sensor Cords
  • Measurement Guide
  • Instruction Manual

Hioki PW3360-21 Clamp-On Power Logger, 90 to 780V, Harmonic Analysis. Great savings PLUS Free Shipping when you order online at EquipTestPro.com.